Robust optimal design of UFLS schemes in Island Power Systems

E. Lobato, M. Rajabdorri, L. Sigrist, I. Egido, A. Ortega

Sustainable Energy, Grids and Networks Vol. 39, pp. 101434-1 - 101434-8

Summary:

Since settings of conventional underfrequency load shedding (UFLS) schemes cannot be adjusted in real-time, this paper proposes a novel robust optimal design method of the UFLS scheme for an island power system (IPS) that once fixed, gives an adequate performance in all possible operating conditions in the IPS. The core of the novel robust optimal design method is the implementation of a synthetic data generation algorithm that covers all the feasible generator operating points, which are further classified into a set of large number (but computationally manageable) representative generation dispatches using clustering techniques. A real-world Spanish island will be used to illustrate the method, where the UFLS robust design will be tested and compared with non-robust UFLS designs tuned using generation dispatches of an actual day of operation provided by both standard and frequency-constrained unit commitment algorithms. Results will show that the proposed robust design avoids frequency constraints violations in contingencies and obtains better frequency metrics.


Spanish layman's summary:

Este artículo propone un método de diseño robusto del esquema UFLS para un sistema eléctrico insular para todos las escenarios de operación posibles. Los resultados en una isla española real muestran que el diseño robusto propuesto evita violaciones de las restricciones de frecuencia en contingencias y obtiene mejores resultados dinámicos.


English layman's summary:

This paper proposes a novel robust optimal design method of the UFLS scheme for an island power system for all possible operating conditions. Results of a real-world Spanish island show that the proposed robust design avoids frequency constraints violations in contingencies and obtains better frequency metrics.

 


Keywords: Frequency stability; under-frequency load shedding; island power systems; unit commitment


JCR Impact Factor and WoS quartile: 4,800 - Q1 (2023)

DOI reference: DOI icon https://doi.org/10.1016/j.segan.2024.101434

Published on paper: September 2024.

Published on-line: May 2024.



Citation:
E. Lobato, M. Rajabdorri, L. Sigrist, I. Egido, A. Ortega, Robust optimal design of UFLS schemes in Island Power Systems. Sustainable Energy, Grids and Networks. Vol. 39, pp. 101434-1 - 101434-8, September 2024. [Online: May 2024]


    Research topics:
  • Isolated systems: islands, microgrids, off-grid : Islands, microgrids, off-grid